In general, the outgoing exhaust gasses are released to atmosphere at over temperature of the dew point of water vapor in waste gases. It is well known that recovering a portion of the waste heat enhances the efficiency of boilers and provides fuel savings. In this study, the potential of recovering waste heat emitted by the hot water boiler chimney in a central heating plant of the selected university was investigated. Energy losses were calculated for six months that the central heating system was in full-load operation. As a result of the calculation, it was determined that recovery of the waste heat can be employed as a combustion air preheater by means of a recuperator. It was stated that 53768 m3 of natural gas savings per year (44.86 TOE/year) can be achieved with the suggested system.
Waste Heat Recovery Recuperator Exhaust Flue Gas Energy Saving
Birincil Dil | İngilizce |
---|---|
Bölüm | Makaleler |
Yazarlar | |
Yayımlanma Tarihi | 1 Ocak 2019 |
Yayımlandığı Sayı | Yıl 2019 Cilt: 20 Sayı: 1 |